Torsional Irregularity in Buildings โ€” IS 1893:2016 | StructLearn
IS 1893 (Part 1) : 2016 ยท Sixth Revision

Torsional Irregularity
in Buildings

A complete student guide to understanding, checking, and designing for torsional irregularity as per Table 5 and Clause 7.8 of IS 1893:2016.

Table 5 โ€” Plan Irregularities
Clause 7.8 โ€” Design Torsion
Amendment No. 2 (2020) Included

What is Torsional Irregularity?

When an earthquake strikes, it shakes a building horizontally. Ideally, every floor should translate (slide) uniformly. But if the building’s centre of mass (CM) and centre of resistance (CR) do not coincide, the building will also twist about its vertical axis โ€” this is called torsional response.

๐Ÿ› Centre of Mass (CM)

The point on a floor through which the resultant inertia force due to earthquake shaking acts. It depends on the distribution of mass (dead load + live load) on the floor slab.

โš™๏ธ Centre of Resistance (CR)

The point through which, when lateral force is applied, the floor undergoes pure translation with no twist. It depends on the stiffness distribution of all lateral load resisting elements (columns, walls, braces).

๐Ÿ“Œ Key Concept โ€” Static Eccentricity (es) The distance between CM and CR at any floor level is called the static eccentricity (es). A non-zero static eccentricity causes torsional moments in the building when earthquake forces are applied.

Plan view of a building floor showing torsional twist due to CM-CR offset

โœ… Regular Building โ€” CM = CR
CM/CR Pure Translation โœ“
No twist. All points displace equally. Safe behaviour.
โš ๏ธ Torsionally Irregular โ€” CM โ‰  CR
CR CM eโ‚› Twist + Translation โš 
One end displaces more than the other โ€” dangerous!

Table 5 โ€” Plan Irregularities Explained

IS 1893:2016 Clause 7.1 lists five types of plan irregularities in Table 5. A building is considered irregular if any one condition is satisfied. Torsional Irregularity is Sl. No. (i) of Table 5.

Sl. No. (i) โ€” Torsional Irregularity

A building is torsionally irregular when both of the following conditions exist simultaneously:

๐Ÿ“
Condition 1 โ€” Displacement Ratio

The maximum horizontal displacement at any point on the extreme edge of the floor (ฮ”max) is more than 1.5 times the minimum horizontal displacement at the far end (ฮ”min) in that direction.

ฮ”max / ฮ”avg > 1.2
As amended by Amendment No. 2 (2020): ratio is now ฮ”m vs ฮ”a = (ฮ”โ‚+ฮ”โ‚‚)/2
๐Ÿ“Š
Condition 2 โ€” Mode Period

The natural period corresponding to the fundamental torsional mode of oscillation is more than that of the first two translational modes along each principal plan direction.

This means the building “wants to twist” more easily than it “wants to slide” โ€” a very dangerous configuration.

โš ๏ธ Amendment No. 2 (November 2020) โ€” Revised Thresholds The 2020 amendment replaced the original 1.5โ€“2.0 ratio bands with a new clearer criterion:
โ€ข ฮ”m is in range 1.2 ฮ”a to 1.4 ฮ”a: Revise configuration + use 3D dynamic analysis
โ€ข ฮ”m > 1.4 ฮ”a: Building configuration shall be revised (not permitted as-is)
where ฮ”a = (ฮ”โ‚ + ฮ”โ‚‚)/2 = average of the two extreme edge displacements.

Summary of All 5 Plan Irregularities (Table 5)

Sl. No. Type Trigger Condition Required Action
(i) Torsional Irregularity ฮ”m > 1.2 ฮ”a AND torsional mode period > translational period 3D Dynamic Analysis
(ii) Re-entrant Corners Plan projection > 15% of overall plan dimension in that direction 3D Dynamic + Flexible Diaphragm
(iii) Floor Slab Discontinuity Cut-outs or openings in floor slab Rigid or Flexible Diaphragm per size
(iv) Out-of-Plane Offsets Lateral force resisting elements have out-of-plane discontinuities Force Enhancement ร—2.5; Drift < 0.2%
(v) Non-Parallel Systems Lateral force resisting elements not along two mutually perpendicular directions Bi-directional seismic loading per 6.3.2.2
๐Ÿ“‹ Clause 7.1 โ€” Important General Rule “An effort shall be made to eliminate irregularities by modifying architectural planning and structural configuration. A building shall be considered irregular for the purposes of this standard, even if any one of the conditions given in Tables 5 and 6 is applicable.”

When is Bi-directional Loading Required?

Clause 6.3.2.2: When the lateral force resisting system is not oriented along two mutually orthogonal directions (see Table 5(v)), the building must be designed for simultaneous bi-directional effects:

Load Combinations โ€” Clause 6.3.2.2
ยฑELx ยฑ 0.3 ELy  and  ยฑ0.3 ELx ยฑ ELy
Where ELx and ELy are earthquake loads along X and Y principal directions respectively.

Torsion โ€” Clause 7.8 in Detail

Even in buildings that are not classified as torsionally irregular, IS 1893 mandates a design eccentricity to account for torsional effects. This is Clause 7.8.

7.8.1 โ€” Why Torsion Must Always Be Designed For

Clause 7.8.1 โ€” Provision Provision shall be made in all buildings for the increase in shear forces on lateral force resisting elements resulting from twisting about the vertical axis, arising due to eccentricity between the centre of mass and centre of resistance at floor levels.

The design forces (from Clause 7.6 โ€” Seismic Coefficient Method, or Clause 7.7.5 โ€” Response Spectrum Method) shall be applied at the displaced centre of mass so as to cause the design eccentricity ed.

7.8.2 โ€” Design Eccentricity Formula

The design eccentricity edi at floor i is the larger of the two values that gives the more severe effect:

Design Eccentricity โ€” Clause 7.8.2
edi = 1.5 esi + 0.05 bi
โ€” OR โ€”
edi = esi โˆ’ 0.05 bi
Whichever gives the more severe effect on lateral force resisting elements
esi

Static Eccentricity at floor i โ€” the distance between Centre of Mass (CM) and Centre of Resistance (CR) at that floor level.

ร— 1.5

Dynamic Amplification Factor โ€” accounts for dynamic amplification of torsional effects during actual earthquake shaking (vs. static analysis).

ยฑ 0.05 bi

Accidental Eccentricity โ€” 5% of the floor plan dimension perpendicular to the earthquake direction. Accounts for uncertainties in mass location, torsional ground motion, etc.

โœ… Important Note for Time History Method The dynamic amplification factor of 1.5 is NOT required when performing structural analysis by the Time History Method. In that case:
edi = esi ยฑ 0.05 bi

Why Two Formulas? โ€” The “More Severe Effect” Explained

The two formulas give eccentricities on opposite sides of the CR. The engineer must check both and design for whichever produces greater forces in the critical lateral force resisting elements.

FormulaPhysical MeaningWhen More Critical
1.5es + 0.05b Eccentricity is amplified and accidental eccentricity adds to it (same side) When natural eccentricity and accidental eccentricity act in same direction โ€” maximises torsion
es โˆ’ 0.05b Accidental eccentricity reduces effective eccentricity (opposite side) When checking elements on the other side of the building โ€” may govern for those elements

Torsion in Open Storey Buildings (Clause 7.10.3)

โš ๏ธ Critical Provision โ€” Open Storey / Soft Storey Buildings When RC structural walls are provided to address soft-storey issues, the design must ensure the building does not gain additional torsional irregularity in plan beyond what already exists. Specifically:
  • Lateral stiffness in open storey shall be โ‰ฅ 80% of storey above
  • Lateral strength in open storey shall be โ‰ฅ 90% of storey above
  • Torsional irregularity assessment must include all elements at all levels

Torsional Irregularity Checker & Design Eccentricity Calculator

Use this tool to check if your building floor qualifies as torsionally irregular per IS 1893:2016 (including Amendment No. 2, 2020), and compute the design eccentricity per Clause 7.8.2.

๐Ÿ”„

Torsional Irregularity Check

Enter floor displacements and eccentricity details below


Part A โ€” Displacement Ratio Check (Amendment No. 2, 2020)

Input the lateral displacements at both extreme edges of the floor in the considered earthquake direction.

Typically the end with larger displacement
The other extreme edge displacement
From modal analysis output
Along X-direction
Along Y-direction

Part B โ€” Design Eccentricity (Clause 7.8.2)

Compute design eccentricity for torsion design.

Distance between CM and CR
Plan width perpendicular to earthquake direction

๐Ÿ“Š Results
โ€”
ฮ”m (max disp, mm)
โ€”
ฮ”a = (ฮ”โ‚+ฮ”โ‚‚)/2 (mm)
โ€”
ฮ”m / ฮ”a Ratio
โ€”
ed Case 1 (m)
โ€”
ed Case 2 (m)

๐Ÿ“‹ Step-by-Step Calculation

๐Ÿ“ Design Eccentricity โ€” Clause 7.8.2

Solved Numerical Problem

Problem Statement

A 6-storey RC building in Seismic Zone IV has the following data at the 3rd floor:
โ€ข ฮ”โ‚ = 22 mm (maximum edge displacement under EQ in X-direction)
โ€ข ฮ”โ‚‚ = 12 mm (displacement at other extreme edge)
โ€ข Static eccentricity es = 1.5 m, Floor width b = 18 m (perpendicular to EQ)
โ€ข Modal analysis gives: Ttor = 1.9 s, T1 = 1.6 s, T2 = 1.4 s
โ€ข Analysis by Response Spectrum Method
Check for torsional irregularity and compute design eccentricity.

Solution

  1. Step 1: Compute ฮ”a (average displacement) ฮ”a = (ฮ”โ‚ + ฮ”โ‚‚) / 2 = (22 + 12) / 2 = 17 mm
  2. Step 2: Identify ฮ”m (maximum) ฮ”m = max(ฮ”โ‚, ฮ”โ‚‚) = 22 mm
  3. Step 3: Compute Displacement Ratio ฮ”m / ฮ”a = 22 / 17 = 1.294
    Since 1.2 ฮ”a = 20.4 mm and 1.4 ฮ”a = 23.8 mm,
    ฮ”m = 22 mm falls in range [20.4, 23.8] โ†’ Torsional Irregularity Zone
  4. Step 4: Check Torsional Mode Period Ttor = 1.9 s > T1 = 1.6 s and Ttor > T2 = 1.4 s
    โ†’ Torsional mode is dominant โ€” both conditions satisfied โœ“
  5. Step 5: Conclusion โ€” Torsional Irregularity Classification Building is torsionally irregular as per Table 5(i).
    Since 1.2ฮ”a โ‰ค ฮ”m โ‰ค 1.4ฮ”a: Revise configuration to bring Ttor < T1 & T2, AND adopt 3D dynamic analysis.
  6. Step 6: Design Eccentricity (Clause 7.8.2)
    Accidental eccentricity = 0.05 ร— b = 0.05 ร— 18 = 0.9 m
    Case 1: ed = 1.5 ร— 1.5 + 0.9 = 2.25 + 0.9 = 3.15 m
    Case 2: ed = 1.5 โˆ’ 0.9 = 0.6 m
    Note: Factor 1.5 applies since RSM is used (not Time History)
    โ†’ Design eccentricity = 3.15 m (Case 1 governs โ€” more severe)
โœ… Final Answer The building is torsionally irregular. The design eccentricity to be used = 3.15 m. The structural configuration must be revised to reduce the torsional mode period, and a full 3D dynamic analysis is mandatory.

Vertical Irregularities โ€” Quick Reference

While Table 5 covers plan irregularities, Table 6 covers vertical irregularities. Together they define when a building is irregular and what analytical method must be used.

Sl. No.TypeDefinitionConsequence
(i) Stiffness Irregularity (Soft Storey) Lateral stiffness of a storey < that of storey above Dynamic Analysis + Inter-storey drift โ‰ค 0.2%
(ii) Mass Irregularity Seismic weight at any floor > 150% of floors below Dynamic Analysis in Zones III, IV, V
(iii) Vertical Geometric Irregularity Horizontal dimension of LFRS in any storey > 125% of storey below Dynamic Analysis in Zones III, IV, V
(iv) In-Plane Discontinuity In-plane offsets of LFRS exceed 20% of plan length Not permitted in Zones III, IV, V
(v) Strength Irregularity (Weak Storey) Lateral strength < 80% of storey above Not permitted
(vi) Floating Columns Column resting on a beam at lower termination level Not permitted as primary LFRS element
(vii) Irregular Oscillation Modes First 3 modes < 65% mass participation, or Tโ‚ & Tโ‚‚ within 10% Ensure 65% mass participation

Key Takeaways for Students

๐Ÿ“
Two Conditions Required Both the displacement ratio (ฮ”m/ฮ”a) AND the torsional mode period condition must be satisfied for torsional irregularity to exist.
๐Ÿ”ข
2020 Amendment Changed the Ratios Old standard used 1.5โ€“2.0 ratio. Amendment No. 2 (2020) replaced this with 1.2ฮ”aโ€“1.4ฮ”a threshold bands.
๐Ÿ—
Design Eccentricity is Mandatory for ALL Buildings Clause 7.8 applies to all buildings, not just irregular ones. Every building must account for accidental + dynamic eccentricity.
โšก
Factor 1.5 is for SCM & RSM Only The dynamic amplification of 1.5 in the eccentricity formula is NOT applied when using Time History Method.
๐Ÿ“Š
3D Analysis is Triggered Torsional irregularity mandates three-dimensional dynamic analysis โ€” not just 2D planar methods.
๐Ÿ”„
Revise Geometry First IS 1893 always says “an effort shall be made to eliminate irregularities”. Architectural redesign is the preferred solution.
๐Ÿ“
0.05b = Accidental Eccentricity The 5% of floor width accounts for uncertainties in mass location, non-uniform live loading, and rotational ground motion components.
๐Ÿงฑ
Open Storeys Add Torsion Risk Adding shear walls in open storeys must not introduce new torsional irregularity โ€” Clause 7.10.3 must be checked.
๐Ÿ“– Standard Reference Summary
  • IS 1893 (Part 1) : 2016 โ€” Criteria for Earthquake Resistant Design of Structures, Part 1: General Provisions and Buildings (Sixth Revision)
  • Amendment No. 1 โ€” September 2017 โ€” Minor corrections
  • Amendment No. 2 โ€” November 2020 โ€” Revised torsional irregularity threshold, open/flexible diaphragm requirements
  • Clause 7.1 + Table 5(i) โ€” Torsional Irregularity definition
  • Clause 7.8 โ€” Design eccentricity for torsion
  • Clause 6.3.2.2 โ€” Bi-directional seismic loading
  • Clause 7.10.3 โ€” Torsion in open storey buildings
StructLearn โ€” IS 1893 Learning Series
Content based on IS 1893 (Part 1):2016 with Amendment No. 1 (2017) & Amendment No. 2 (2020) | Bureau of Indian Standards
Educational resource only. Always refer to the official BIS standard for design practice.
`;

Leave a Comment