Views in the last 30 days: 9
Estimated read time: 5 minute(s)
Chiller Capacity Calculator — What It Is, How It Works, and How to Use It (with a Full Worked Example)
This interactive calculator sizes central chillers from first principles. It turns your room-by-room loads, ventilation targets, and design allowances into a clean recommendation: peak kW/TR, chilled-water flow, chiller count & size (with N or N+1), plus a quick cost & energy snapshot. SI/Imperial toggles, sector presets, and standards hints are built in.
1) What this calculator does
- Segments your building (zones like open office, conference, server, OR/ICU, kitchen, cleanroom, etc.).
- Applies sensible/latent densities (W/m²) or your direct overrides (kW/TR).
- Calculates ventilation load from ACH × volume and a user-set enthalpy delta.
- Rolls in diversity, piping gain, and safety to get a robust peak kW/TR.
- Derives CHW flow from ΔT; recommends chiller count & size (N or N+1).
- Estimates budget cost (equipment → installed → with markup) and annual energy.
- Outputs a clean HTML report with KPIs, tables, and change log (print-ready).
2) How the math works (short version)
- Segment loads
Sensible:
Qs,i = Ai × qs / 1000
kW; Latent:Ql,i = Ai × ql / 1000
kW. (Or enter overrides in kW/TR.) - Ventilation (optional ACH)
Qvent,i ≈ ρ × (A × H) × ACH / 3600 × Δh
kW, with ρ≈1.2 kg/m³ and Δh (kJ/kg) set by you. - Allowances
Qbase = Σ(Qs+Ql) + Qvent + Qproc
Q′ = Qbase × fdiversity
→ piping gain → safety →Qpeak
. - CHW flow
SI:
L/s = Q(kW) / (4.186 × ΔT[K])
; IP:gpm = 24 × (TR) / ΔT[°F]
. - Chillers
Choose N or N+1. If N+1:
(n−1) × size ≥ TRpeak
. - Energy & cost
kWin = TR × (kW/ton) × loadFactor
→ annual kWh → tariff; Cost = installed TR × unit rate × install factor × (1+markup).
Full methodology, symbols & unit math
Same detailed methodology used inside the calculator’s “Methodology” panel. Standards notes are shown inline as “Values derived from <Standard> (user must verify).”
3) How to use the calculator
Related tools: You might also like Cooling Load Calculator, Duct Sizing Calculator, Pipe Design Calculator, and Psychrometrics – Moist Air Guide.
4) Worked example — Office floor (full calculation)
Target: Size central chiller plant for an office floor with open office, conference suite, and a small server room. Use SI for the math; show key IP equivalents.
Inputs & assumptions
- Segments (height H = 3.2 m, Δh = 12 kJ/kg, ACH-based ventilation):
Segment | Area (m²) | Sensible (W/m²) | Latent (W/m²) | Overrides (kW) | ACH |
---|---|---|---|---|---|
Open Office | 600 | 70 | 15 | — | 2 |
Conference Suite | 200 | 100 | 25 | — | 4 |
Server Room | 50 | — | — | Sensible = 30, Latent = 0 | 6 |
- Allowances: Diversity 0.90; Piping gain 3%; Safety 10%.
- CHW: 7 → 15 °C (ΔT = 8 K).
- Selection: N+1 redundancy.
- Costing (India): Water-cooled unit rate ₹20,000/TR; install factor 1.5; markup 10%.
- Energy: kW/ton = 0.70; hours/year = 3,000; avg load factor = 0.55; tariff ₹9/kWh.
Step-by-step math
- Segment loads
Open Office:
Qs = 600×70/1000 = 42.00 kW
,Ql = 600×15/1000 = 9.00 kW
Conference:Qs = 200×100/1000 = 20.00 kW
,Ql = 200×25/1000 = 5.00 kW
Server Room (override):Qs = 30.00 kW
,Ql = 0.00 kW
Totals: Sensible =92.00
kW; Latent =14.00
kW; Internal =106.00
kW. - Ventilation (ACH-based) with ρ=1.2 kg/m³, Δh=12 kJ/kg
Volume per segment = A×H. Load ≈
1.2×Volume×ACH/3600×Δh
.- Open Office: V=600×3.2=1920 m³ →
1.2×1920×2/3600×12 = 15.36
kW - Conference: V=200×3.2=640 m³ →
1.2×640×4/3600×12 = 10.24
kW - Server: V=50×3.2=160 m³ →
1.2×160×6/3600×12 = 3.84
kW
29.44
kW - Open Office: V=600×3.2=1920 m³ →
- Allowances
Qbase = 106.00 + 29.44 = 135.44
kW Diversity:Q′ = 135.44 × 0.90 = 121.896
kW Piping:Q″ = 121.896 × 1.03 = 125.55288
kW Safety:Qpeak = 125.55288 × 1.10 = 138.10817 kW
- Convert to TR (1 TR = 3.517 kW):
TRpeak = 138.10817 / 3.517 = 39.27 TR
- CHW flow
SI:
L/s = 138.10817 / (4.186 × 8) = 4.124 L/s
IP: ΔT=8 K=14.4 °F →gpm = 24×TR/ΔT = 24×39.27/14.4 = 65.45 gpm
- Selection (N+1)
Choose 3 × 20 TR. Check:
(3−1) × 20 = 40 TR ≥ 39.27 TR
✓ Installed nameplate = 60 TR. - Budget cost
Equipment =
60 × ₹20,000 = ₹1,200,000
Installed =×1.5 = ₹1,800,000
With markup (10%) =₹1,800,000 × 1.10 = ₹1,980,000
- Annual energy
Input kW at average =
TR × kW/ton × loadFactor = 39.27 × 0.70 × 0.55 = 15.12 kW
Annual kWh =15.12 × 3,000 = 45,355 kWh
Energy cost (@₹9/kWh) =₹408,199 / year
Peak Cooling
CHW Flow
Recommended Plant
Budget Installed
Segment breakdown (kW)
Bars show sensible+latent per segment; ventilation shown in the table below.
Segment | Area (m²) | Sensible (kW) | Latent (kW) | Total (kW) | ACH Vent (kW) |
---|---|---|---|---|---|
Open Office | 600.0 | 42.00 | 9.00 | 51.00 | 15.36 |
Conference Suite | 200.0 | 20.00 | 5.00 | 25.00 | 10.24 |
Server Room | 50.0 | 30.00 | 0.00 | 30.00 | 3.84 |
Totals | 92.00 | 14.00 | 106.00 | 29.44 |
Use in the calculator: Enter the same segments, set ACH-based ventilation, allowances, ΔT=8 K, choose N+1 and India (Water-cooled). Click Calculate → the KPIs will match these numbers. Then Generate Report for a print-ready sheet.
5) Notes, tips & references
- Validation: Always sanity-check W/m² seeds against your project’s envelope, lighting, equipment and occupancy. Presets are starting points.
- Ventilation: If your jurisdiction mandates L/s·person or L/s·m² (e.g., ASHRAE 62.1/ISHRAE/CIBSE), convert to ACH or directly compute a ventilation kW and enter it as a manual global value.
- ΔT strategy: 8–10 K reduces pumping power; validate coil performance and valve authority.
- N+1 choices: For small TR peaks, 3× modules often land better than 2× big units for serviceability and turn-down.
- Energy KPI: kW/ton is a planning value; verify AHRI-rated performance and part-load curves before final selections.
- AHRI 550/590 performance rating for water-chilling packages.
- ASHRAE Fundamentals / 90.1, ISHRAE Handbook (India), CIBSE Guide B for typical setpoints and practices.
Values derived from <Standard>, clause ranges vary; users must verify against current editions and local codes.