Design Eccentricity | IS 1893 (Part 1): 2016 | Learning Resource
IS 1893 (Part 1) : 2016 · Clause 7.8.2

Design Eccentricity
1.5eₛ ± 0.05b Explained

A complete student guide to torsional seismic design — from definitions to interactive calculations. Covers Clause 7.8 of IS 1893 (Part 1): 2016 (Sixth Revision).

📘 IS 1893 (Part 1): 2016 🏛️ Seismic Coefficient & Response Spectrum Methods 🧮 Interactive Calculator Included

Why Does Torsion Happen in Buildings?

Before jumping to formulas, let’s understand the physical problem that IS 1893 is solving.


Centre of Mass (CM)

The Centre of Mass is the point through which the resultant inertia (earthquake) force acts during shaking. It depends on the distribution of mass — heavier parts of the floor pull the CM towards them.

💡 Simple analogy: Imagine the floor balanced on a pin. The CM is the balance point when you consider all the mass loaded on it.

Clause 4.4  IS 1893 (Part 1): 2016

Centre of Resistance (CR)

The Centre of Resistance is the point through which the resultant lateral stiffness of the floor acts. It depends on the distribution of lateral stiffness — stiffer columns/walls pull the CR towards them.

💡 Simple analogy: If you push the floor sideways with a force at the CR, the floor translates without rotating. Push elsewhere → it twists!

Clause 4.5  IS 1893 (Part 1): 2016

FLOOR PLAN (View from Above) CM Centre of Mass CR Centre of Resistance eₛ b = floor plan dimension perpendicular to shaking SHAKING → Stiff wall (pulls CR right)

When CM ≠ CR, the earthquake force creates a twisting moment (torque) about the vertical axis — this is the torsion IS 1893 accounts for.

The Logic Chain: From Mass Offset to Design Force

Earthquake force acts at the Centre of Mass (CM)

During shaking, inertia forces are distributed over the floor and their resultant acts at the CM.

CM and CR rarely coincide

Due to irregular mass distribution or irregular stiffness layout, CM and CR are offset. This offset = Static Eccentricity (eₛ).

The force at CM creates a torsional moment

Force × offset distance = Torque. This torque twists the building about the vertical axis, creating additional forces in the lateral load resisting elements.

Real-world eccentricity is amplified dynamically

Static eccentricity underestimates the actual torsion. IS 1893 applies a 1.5× dynamic amplification factor to account for dynamic coupling effects.

Accidental eccentricity is added/subtracted

Even if CM and CR are at the same point, uncertainties in mass distribution, unexpected loads, ground motion rotational components etc. cause accidental eccentricity = ±0.05b.

Design uses the WORST CASE of the two combinations

Both 1.5eₛ + 0.05b and eₛ − 0.05b are checked. The one that causes larger forces in the element governs.

Static Eccentricity (eₛ)

Defined in Clause 4.6.2:

Definition
eₛ = |xCM − xCR|
Distance between Centre of Mass and Centre of Resistance at floor i

This is a purely geometric/structural parameter determined from the building layout. It is different for each floor.

Floor Plan Dimension (b)
Definition
b = floor plan dimension perpendicular to the direction of seismic force
If shaking is along X → b is the Y dimension of the floor
⚠️ Common mistake: Students often use the dimension parallel to force. It must be perpendicular to the direction of seismic shaking!
Why Two Formulas? Understanding the ± Logic

Case 1:  edᵢ = 1.5eₛ + 0.05b

The dynamic amplification (1.5×) and accidental eccentricity both act in the SAME direction, pushing the effective centre of mass further away from CR. This is the additive case.

When critical: Governs for elements on the side far from CR (elements near the torsionally flexible edge).

Case 2:  edᵢ = eₛ − 0.05b

The accidental eccentricity opposes the static eccentricity. This may seem to reduce the torsion — but it can reverse the direction or make another element critical.

Note: The 1.5 amplification is NOT applied here — only static eₛ minus the accidental offset is used.
The governing rule (IS 1893 Clause 7.8.2): Use whichever combination gives the more severe effect on the lateral force resisting elements. Both cases must be checked; the element is designed for the worst.
The 1.5 Factor: Dynamic Amplification Explained

IS 1893 (Part 1): 2016, Clause 7.8.2 states explicitly:

Clause Explanation
“The factor 1.5 represents dynamic amplification factor, and 0.05 represents the extent of accidental eccentricity.”

🔬 Why 1.5× for dynamic amplification?

During dynamic (earthquake) loading, the actual oscillation of the building amplifies the torsional response beyond what a static analysis predicts. This amplification arises due to coupling between translational and torsional modes of vibration. The factor 1.5 is a code-prescribed amplification to convert the static eccentricity to an equivalent dynamic design value.

📏 Why 0.05b for accidental eccentricity?

Even in a perfectly symmetric building, uncertainties exist: actual mass positions differ from computed ones, live load is not uniformly placed, stiffness varies with temperature, construction tolerances exist, and ground motion has rotational components. The 5% of plan dimension accounts for all these real-world uncertainties.

⚠️ Important Exception (IS 1893 Cl. 7.8.2): The 1.5 amplification factor need NOT be used when performing structural analysis by the Time History Method. For Time History analysis, only accidental eccentricity (±0.05b) is added to the computed static eccentricity.

Clause 7.8 — Torsion Provisions


Clause 7.8.1 — Torsion Provision

Provision shall be made in all buildings for increase in shear forces on the lateral force resisting elements resulting from twisting about the vertical axis of the building, arising due to eccentricity between the centre of mass and centre of resistance at floor levels.

The design forces calculated (as per Clauses 7.6 and 7.7.5) shall be applied at the displaced centre of mass so as to cause design eccentricity (as given by Clause 7.8.2) between the displaced CM and CR.

Clause 7.8.2 — Design Eccentricity Formula
🔑 Core Formula — IS 1893 Clause 7.8.2
edᵢ = Max { 1.5eₛ + 0.05b  |  eₛ − 0.05b }
“Whichever gives the more severe effect on lateral force resisting elements”
edᵢ = design eccentricity at floor i (m)
eₛ = static eccentricity at floor i (m)
b = floor plan dimension ⊥ to seismic force (m)
1.5 = dynamic amplification factor
0.05 = accidental eccentricity ratio
Applicable methods: Seismic Coefficient Method (SCM) and Response Spectrum Method (RSM).
NOT required for: Time History Analysis (1.5 amplification is not applied; only ±0.05b is added).
Side-by-Side: Two Design Eccentricity Cases
ParameterCase 1: 1.5eₛ + 0.05bCase 2: eₛ − 0.05b
Dynamic Amplification (1.5×)✓ Applied✗ Not applied
Accidental Eccentricity+0.05b (adds to eₛ side)−0.05b (opposes eₛ)
Resultant ed vs eₛAlways ≥ 1.5eₛMay be less than eₛ; can be negative
Critical for element at…Far flexible edge (away from CR)Near stiff edge; or when torsion reverses
Governs when…Element is on the torsionally flexible sideAccidental reversal makes an element worse
Used inSCM & RSMSCM & RSM
Related Clauses and Definitions
ClauseTopicKey Content
4.4Centre of Mass (CM)Point through which resultant inertia force acts. Depends on mass distribution.
4.5Centre of Resistance (CR)Point through which resultant internal resistance acts with no floor rotation.
4.6.1Design Eccentricity (edᵢ)Value of eccentricity used in torsion design calculations at floor i.
4.6.2Static Eccentricity (eₛ)Distance between CM and CR at floor i.
7.8.1Torsion ProvisionAll buildings must account for torsion due to CM-CR offset.
7.8.2Design Eccentricity Formulaedᵢ = max{1.5eₛ + 0.05b, eₛ − 0.05b}
Table 5(i)Torsional IrregularityMax displacement > 1.2× average displacement; torsional mode period check.
6.4.2Design Seismic Coefficient AhAh = (Z/2)(I/R)(Sa/g); the lateral force basis.
Torsional Moment Calculation

Once the design eccentricity is known, the design torsional moment at each floor is computed as:

Torsional Moment at Floor i
Mᵢ = Qᵢ × edᵢ
Mᵢ = torsional moment at floor i (kN·m)
Qᵢ = lateral seismic force at floor i (kN)
edᵢ = design eccentricity at floor i (m)

This torsional moment is then distributed to each lateral load resisting element (column, shear wall, frame) in proportion to their stiffness and their distance from the CR.

Torsional Irregularity (Table 5, IS 1893)

A building is torsionally irregular when the maximum horizontal displacement at one edge exceeds 1.2× the average of the displacements at both edges (as per Amendment No. 2). Additional checks:

  • If Δₘ is in range 1.2Δₐ to 1.4Δₐ → revise configuration AND use 3D dynamic analysis
  • If Δₘ > 1.4Δₐ → structural configuration must be revised
where Δₐ = (Δ₁ + Δ₂)/2, Δ₁ = smaller displacement at one end, Δ₂ = larger displacement at other end.

Design Eccentricity Calculator

Compute design eccentricity per IS 1893 (Part 1): 2016, Clause 7.8.2 for one or multiple floors. The calculator shows step-by-step working and highlights the governing case.


Building & Floor Parameters

🏢 Floor 1
Distance between CM and CR (always positive)
Perpendicular to direction of shaking
From seismic analysis (optional, for moment)
Results Summary

Worked Numerical Examples


Example 1 — Basic Single Floor Calculation

Problem: A G+4 storey RC building in Seismic Zone IV has the following data for 2nd floor:

  • Static eccentricity, eₛ = 0.9 m
  • Floor plan dimension perpendicular to seismic force, b = 15 m
  • Analysis method: Seismic Coefficient Method

Find: Design eccentricity edᵢ.

Step-by-Step Solution

Given:  eₛ = 0.9 m  |  b = 15 m  |  Method: SCM
Calculate 0.05b:  0.05 × 15 = 0.75 m
Case 1 (Cl. 7.8.2):  1.5 × eₛ + 0.05b = 1.5 × 0.9 + 0.75 = 1.35 + 0.75 = 2.10 m
Case 2 (Cl. 7.8.2):  eₛ − 0.05b = 0.9 − 0.75 = 0.15 m
Governing ed:  Both cases must be checked. Case 1 gives larger torsion on the flexible side.
Design Eccentricities: ed = 2.10 m (Case 1) and ed = 0.15 m (Case 2). Design each element for its more critical case.
Example 2 — With Torsional Moment Calculation

Problem: For a floor in an office building:

  • eₛ = 1.2 m, b = 20 m
  • Lateral seismic force at this floor, Qᵢ = 350 kN
  • Method: Response Spectrum Method

Find: ed and torsional moments for both cases.

Step-by-Step Solution

Given:  eₛ = 1.2 m, b = 20 m, Qᵢ = 350 kN
0.05b:  0.05 × 20 = 1.0 m
Case 1 — ed:  1.5 × 1.2 + 1.0 = 1.8 + 1.0 = 2.80 m
Case 1 — Torsional Moment:  M₁ = 350 × 2.80 = 980 kN·m
Case 2 — ed:  1.2 − 1.0 = 0.20 m
Case 2 — Torsional Moment:  M₂ = 350 × 0.20 = 70 kN·m
✅ Case 1 governs for elements on the flexible side: Torsional Moment = 980 kN·m
Case 2 (70 kN·m) may govern for elements on the opposite side if it reverses the sign of shear.
Example 3 — Time History Method (Exception Case)

Problem: Same building data as Example 2, but using Time History Analysis. eₛ = 1.2 m, b = 20 m.

Step-by-Step Solution (THM)

Method:  Time History Method
Exception applies:  The 1.5 dynamic amplification factor is NOT used (Cl. 7.8.2 proviso)
0.05b:  0.05 × 20 = 1.0 m
Case 1 — ed (THM):  eₛ + 0.05b = 1.2 + 1.0 = 2.20 m (NOT 1.5×eₛ)
Case 2 — ed (THM):  eₛ − 0.05b = 1.2 − 1.0 = 0.20 m
Key difference from SCM/RSM: For SCM/RSM → ed Case 1 = 2.80 m; For THM → ed Case 1 = 2.20 m. The THM inherently captures the dynamic amplification in the time-history response itself, so 1.5× is not additionally needed.
Example 4 — Multi-Floor Design Eccentricity Table

A 5-storey building (SCM). Each floor has different eccentricity and plan dimensions:

Flooreₛ (m)b (m)0.05b (m)1.5eₛ+0.05b (m)eₛ−0.05b (m)Remarks
5th0.5100.501.250.00ed = 1.25 m; Case 2 = 0 (boundary)
4th0.8120.601.800.20ed = 1.80 m governs flexible side
3rd1.0150.752.250.25ed = 2.25 m governs
2nd1.2150.752.550.45ed = 2.55 m governs
1st0.6180.901.80−0.30ed = 1.80 m; Note negative Case 2!
🔍 Observation at 1st floor: Case 2 gives ed = −0.30 m (negative). This means the accidental eccentricity reverses the direction of torsion. This reversed torsion must also be checked for elements on the now-critical side!

Frequently Asked Questions


Q1. What if eₛ = 0 (symmetric building)? Is torsion zero?

No! Even if eₛ = 0 (CM coincides with CR), there is still accidental eccentricity. The formulas become:

When eₛ = 0
Case 1:  1.5 × 0 + 0.05b = +0.05b
Case 2:  0 − 0.05b = −0.05b

So a “symmetric” building still has an effective eccentricity of ±5% of its plan dimension for torsion design. This is why IS 1893 requires torsion provisions for ALL buildings.

Q2. Can design eccentricity be negative? What does it mean?

Yes. When eₛ < 0.05b, Case 2 (eₛ − 0.05b) gives a negative value. A negative ed means the effective torsion is in the opposite direction to what the static eccentricity suggests. This can load elements on the opposite side more severely. Always check all lateral load resisting elements under both cases.

Q3. Is ‘b’ the length or width of the building?

‘b’ is specifically the floor plan dimension perpendicular to the direction of seismic force. For example:

  • If seismic force is applied along the X-direction → b = Y-dimension of the floor
  • If seismic force is applied along the Y-direction → b = X-dimension of the floor

Since seismic analysis is done for both X and Y directions separately, ‘b’ takes a different value for each direction of analysis.

Q4. Why is the 1.5 factor not used in Time History Analysis?

The 1.5 dynamic amplification factor is needed when using the Seismic Coefficient Method or Response Spectrum Method because these are approximate methods that use simplified (smoothed) spectral values and don’t fully capture dynamic coupling between translational and torsional modes.

In the Time History Method, the building is analysed with actual ground motion records step-by-step. The dynamic response (including mode coupling and torsional amplification) is inherently computed in the analysis itself. So the 1.5 factor would be double-counting the dynamic effect.

Q5. Is design eccentricity the same for all storeys?

No. Design eccentricity is calculated independently for each floor. The CM can shift from floor to floor (if mass distribution varies), the CR can shift (if column/wall stiffness changes with height), and the plan dimension b may vary in setback buildings. Therefore eₛ, b, and hence edᵢ must be computed separately for each floor level.

Q6. How is the “more severe effect” determined in practice?

For each lateral force resisting element (frame, shear wall, column), you calculate the shear force under:

  • Direct shear (from translational response) + torsional shear using edᵢ from Case 1
  • Direct shear + torsional shear using edᵢ from Case 2

The maximum (absolute value) of these two combinations governs the design of that element. Elements on different sides of the building will be governed by different cases.

Q7. What is the difference between static and design eccentricity?
PropertyStatic Eccentricity (eₛ)Design Eccentricity (edᵢ)
DefinitionActual distance CM to CRCode-prescribed value for design
BasisStructural geometry and masseₛ × amplification ± accidental
ValueSingle value ≥ 0Two values: Case 1 and Case 2
PurposeInput to design eccentricity formulaUsed to calculate torsional moment
Always > eₛ?Case 1 always ≥ 1.5eₛ; Case 2 may be < eₛ
Q8. Which IS 1893 clauses apply when eₛ is very large (highly irregular plan)?

When torsional irregularity is significant, IS 1893 Table 5(i) requires:

  • Check if building falls under torsional irregularity (Δₘ vs Δₐ check)
  • If Δₘ > 1.2Δₐ to 1.4Δₐ: revise configuration AND perform 3D dynamic analysis
  • If Δₘ > 1.4Δₐ: building configuration must be revised entirely
  • Use 3D modelling to properly capture torsional modes and response

The simple design eccentricity approach (Cl. 7.8.2) is a simplified method suitable for regular structures. Highly irregular structures need more rigorous treatment.

IS 1893 Reference Tables & Data


Table 3 — Seismic Zone Factor Z
Seismic ZoneZIntensity (MSK)
II (Low)0.10VI or less
III (Moderate)0.16VII
IV (Severe)0.24VIII
V (Very Severe)0.36IX and above
Importance Factor I
Structure TypeI
Critical / Lifeline structures1.5
Business continuity structures1.2
All others (residential, offices)1.0
Design Seismic Coefficient Formula (Cl. 6.4.2)
Horizontal Seismic Coefficient
Aₕ = (Z/2) × (I/R) × (Sₐ/g)
Z = zone factor (Table 3)
I = importance factor
R = response reduction factor
Sₐ/g = spectral acceleration coefficient
Summary: Design Eccentricity Quick Reference
ScenarioFormulaNote
SCM or RSM — Case 11.5eₛ + 0.05bDynamic amplification + accidental
SCM or RSM — Case 2eₛ − 0.05bReversed accidental eccentricity
Time History — Case 1eₛ + 0.05bNo 1.5× (THM captures dynamics)
Time History — Case 2eₛ − 0.05bSame as SCM/RSM Case 2
Symmetric building (eₛ=0)±0.05bMinimum accidental eccentricity
Torsional momentMᵢ = Qᵢ × edᵢQᵢ = lateral force at floor i
Common Mistakes to Avoid
  • Using b as the dimension parallel to force — b must be perpendicular to the seismic force direction
  • Forgetting both cases — both ed values must be checked; using only Case 1 is incomplete
  • Applying 1.5× in Time History analysis — the amplification is not required for THM
  • Same ed for all floors — edᵢ must be computed separately for each floor
  • Ignoring negative ed (Case 2) — negative values indicate reversal of torsion and must be checked
  • Using eₛ from one direction for both X and Y — eₛ may differ for X and Y shaking directions

Based on IS 1893 (Part 1): 2016 (Sixth Revision) — Criteria for Earthquake Resistant Design of Structures | Educational Resource | Not a substitute for the original standard

Leave a Comment