NFPA 13 Pipe Sizing

๐Ÿ“ NFPA 13 Pipe Sizing Explained: Schedule vs. Hydraulic Calculation

Views in the last 30 days: 14

Estimated read time: 3 minute(s)


๐Ÿš€ Introduction: Why Pipe Sizing Matters in Sprinkler Systems

Imagine a fire sprinkler system as the arteries of a building โ€” if the pipes are not sized properly, water may not reach the sprinklers in time to fight a fire!
Thatโ€™s why NFPA 13 provides two primary ways to size pipes:

  • โœ… Pipe Schedule Method
  • โœ… Hydraulic Calculation Method

Let’s dive deep into each! ๐ŸŠโ€โ™‚๏ธ


๐Ÿ› ๏ธ 1. What is Pipe Schedule Method?

The Pipe Schedule Method is a prescriptive method.
This means it gives you ready-made tables that tell you:

  • What pipe size you need
  • Based on number of sprinklers, hazard level, and system type

๐Ÿ‘‰ You don’t have to calculate flow and pressure drop for each pipe!

When can you use it?

  • Light Hazard or Ordinary Hazard occupancies (โœ…)
  • Small projects or extensions to old systems (โœ…)
  • New systems less than 5000 ftยฒ (465 mยฒ) (โœ…)
  • ONLY if the water supply can maintain minimum residual pressures at required flows!

Important Reference:

  • Chapter 19.2.2 of NFPA 13 Chapter 19
  • Table 19.2.2.1 shows minimum residual pressure and flow needed!
Occupancy Classification Minimum Residual Pressure Required Acceptable Flow at Base of Riser
(Including Hose Stream Allowance)
Duration (minutes)
Light Hazard 15 psi (1.0 bar) 500โ€“750 gpm (1900โ€“2850 L/min) 30 or 60
Ordinary Hazard 20 psi (1.4 bar) 850โ€“1500 gpm (3200โ€“5700 L/min) 60 or 90

๐Ÿง  2. What is Hydraulic Calculation Method?

The Hydraulic Calculation Method is a performance-based method.
Here, you have to calculate:

  • Water flow (gpm) ๐Ÿ’ง
  • Pressure loss in pipes ๐Ÿ“‰
  • Friction losses in fittings ๐Ÿ”ฉ
  • Velocities ๐Ÿš€

You must ensure that enough pressure and water reach every sprinkler, even the furthest ones!

Important Reference:

  • Chapter 28.2 of NFPA 13 Chapter 28

๐Ÿงฎ Main Formula Used:

Hazen-Williams Equation

Where:

  • p = Frictional pressure loss (psi/ft)
  • Q = Flow rate (gallons per minute, gpm)
  • C = Roughness coefficient (dimensionless; 120 for steel)
  • d = Inside diameter of pipe (inches)

Thereโ€™s also another advanced formula for antifreeze systems (Darcy-Weisbach), but for most fire sprinkler piping, Hazen-Williams is enough! ๐ŸŒŸ


๐Ÿ”ฅ When to Use Each Method?

ScenarioBest Method
Small system (<5000 ftยฒ)Pipe Schedule Method
Extension of an old systemPipe Schedule Method
Large buildingsHydraulic Calculation Method
High-rise, warehouses, data centersHydraulic Calculation Method
Extra Hazard areas (Group 1 or 2)Hydraulic Calculation Method

๐Ÿ›‘ Limitations and Cautions!

  • ๐Ÿšซ Pipe Schedule Method cannot be used for Extra Hazard occupancies.
  • ๐Ÿšซ Pipe Schedule Method assumes a strong water supply.
  • ๐Ÿšซ Hydraulic Calculation Method needs expertise and more detailed design.

๐Ÿ’ฌ Bonus Tip:

๐Ÿ‘‰ If in doubt, always prefer the Hydraulic Calculation Method!
It gives real-world confidence that your design will actually perform during a fire emergency. ๐Ÿ”ฅ

Leave a Comment